Airflow & Rack Thermal Density Calculator
Calculate the airflow equipment or a rack needs to carry away its heat for a chosen inlet-to-outlet temperature rise, corrected for altitude, and check inlet temperature against the recommended envelope.
Results
- Required airflow
- 1,775 CFMcalculated
- Required airflow
- 3,015 m³/hcalculated
- Air density
- 1.188 kg/m³calculated
- Outlet temperature
- 36 °Ccalculated
What it calculates
- Required airflow (CFM, m³/h)
- Air density at altitude
- Outlet temperature
- Inlet temperature check
Worked example
Using the default inputs below; change any input above to recalculate.
| Heat load | 12000 W |
|---|---|
| Air temperature rise (ΔT) | 12 °C |
| Inlet temperature | 24 °C |
| Altitude | 0 m |
| Required airflow | 1,775 CFM | calculated |
|---|---|---|
| Required airflow | 3,015 m³/h | calculated |
| Air density | 1.188 kg/m³ | calculated |
| Outlet temperature | 36 °C | calculated |
Methodology
Heat carried by air: Q = ṁ × c_p × ΔT, with c_p ≈ 1005 J/(kg·K). Volumetric flow = Q ÷ (ρ × c_p × ΔT). Air density uses the standard atmosphere for altitude and the ideal-gas correction for inlet temperature.
Formulas
- Airflow
- V̇ = Q ÷ (ρ × c_p × ΔT)
- Sea-level shortcut
- CFM ≈ 3.16 × W ÷ ΔT(°F)
Assumptions
- Dry air; humidity effects ignored.
Limitations
- Recirculation and bypass air in real rooms raise required supply airflow.