Airflow & Rack Thermal Density Calculator

Calculate the airflow equipment or a rack needs to carry away its heat for a chosen inlet-to-outlet temperature rise, corrected for altitude, and check inlet temperature against the recommended envelope.

Results

Required airflow
1,775 CFM
Required airflow
3,015 m³/h
Air density
1.188 kg/m³
Outlet temperature
36 °C

What it calculates

  • Required airflow (CFM, m³/h)
  • Air density at altitude
  • Outlet temperature
  • Inlet temperature check

Worked example

Using the default inputs below; change any input above to recalculate.

Inputs
Heat load12000 W
Air temperature rise (ΔT)12 °C
Inlet temperature24 °C
Altitude0 m
Results
Required airflow1,775 CFMcalculated
Required airflow3,015 m³/hcalculated
Air density1.188 kg/m³calculated
Outlet temperature36 °Ccalculated

Methodology

Heat carried by air: Q = ṁ × c_p × ΔT, with c_p ≈ 1005 J/(kg·K). Volumetric flow = Q ÷ (ρ × c_p × ΔT). Air density uses the standard atmosphere for altitude and the ideal-gas correction for inlet temperature.

Formulas

Airflow
V̇ = Q ÷ (ρ × c_p × ΔT)
Sea-level shortcut
CFM ≈ 3.16 × W ÷ ΔT(°F)

Assumptions

  • Dry air; humidity effects ignored.

Limitations

  • Recirculation and bypass air in real rooms raise required supply airflow.