Data Centre Capacity, Power & Floor-Space Planner
Plan a data hall from rack count and density: IT load, facility power at PUE, cooling in kW and tons, annual energy and cost, and white-space and total floor area.
Results
- IT load
- 240 kWcalculated
- Facility power
- 360 kWcalculated
- Cooling (IT heat)
- 240 kW · 68.2 TRcalculated
- Annual energy
- 31,53,600 kWhcalculated
- Annual energy cost
- ₹2.52 crorecalculated
- White space
- 56 m²estimated
- Total floor area
- 90 m²estimated
What it calculates
- IT load
- Facility power
- Cooling capacity
- Annual energy and cost
- White space and total floor area
Worked example
Using the default inputs below; change any input above to recalculate.
| Racks | 20 |
|---|---|
| Average load per rack | 12 kW |
| PUE | 1.5 |
| White space per rack (incl. aisles) | 2.8 m² |
| Support space factor | 1.6 |
| Tariff | 8 ₹/kWh |
| IT load | 240 kW | calculated |
|---|---|---|
| Facility power | 360 kW | calculated |
| Cooling (IT heat) | 240 kW · 68.2 TR | calculated |
| Annual energy | 31,53,600 kWh | calculated |
| Annual energy cost | ₹2.52 crore | calculated |
| White space | 56 m² | estimated |
| Total floor area | 90 m² | estimated |
Methodology
IT load = racks × kW per rack. Facility power = IT × PUE. Cooling must remove the IT heat (1 kW = 3,412 BTU/h; 12,000 BTU/h per ton). Floor area uses your planning assumptions for space per rack and support space.
Formulas
- Facility
- P = racks × kW × PUE
- Area
- A = racks × area_per_rack × support_factor
Assumptions
- Average, not peak, rack load for energy.
Limitations
- Floor-space factors vary greatly by design; treat as early planning only.