Cooling & Heat Load Calculator

Calculate the heat a room or data hall must reject — IT load plus UPS losses, lighting and people — in watts, BTU/h and tons of refrigeration, and size cooling units with redundancy.

Results

Total heat load
43.1 kW
Heat load
1,47,063 BTU/h
Tons of refrigeration
12.26
Cooling units
3 × 30 kW
Facility power at PUE
60 kW

What it calculates

  • Total heat load
  • BTU/h and tons of refrigeration
  • Cooling units with redundancy
  • Facility power at PUE

Worked example

Using the default inputs below; change any input above to recalculate.

Inputs
IT load40 kW
UPS and distribution losses6 % of IT
Lighting500 W
People in the room2
Cooling unit capacity30 kW
Spare cooling units1
PUE1.5
Results
Total heat load43.1 kWcalculated
Heat load1,47,063 BTU/hcalculated
Tons of refrigeration12.26calculated
Cooling units3 × 30 kWcalculated
Facility power at PUE60 kWcalculated

Methodology

Almost all electrical power consumed by IT equipment becomes heat. Heat load adds UPS/distribution losses, lighting and people (≈100 W each). 1 W = 3.412 BTU/h; 1 ton of refrigeration = 12,000 BTU/h.

Formulas

BTU/h
Q = W × 3.412
Tons
TR = BTU/h ÷ 12,000

Assumptions

  • Sensible heat only; latent loads and envelope gains are not included.

Limitations

  • Use a mechanical engineer's design for building cooling.