Liquid Cooling & Radiator Sizing Calculator

Calculate the coolant flow needed to absorb a heat load at a chosen coolant temperature rise, for water or glycol mixtures, and estimate radiator size for workstation loops.

Rule of thumb near a 10 °C coolant-to-air difference with moderate fan speed; check the radiator's datasheet curves.

Results

Coolant flow
1.73 L/min
Mass flow
0.029 kg/s
Radiator sections (120 mm)
12

Pump head and pressure drop are not calculated; check that the pump delivers the flow at the loop's pressure drop.

What it calculates

  • Coolant flow rate (L/min)
  • Mass flow
  • Radiator sections (rule of thumb)

Worked example

Using the default inputs below; change any input above to recalculate.

Inputs
Heat load1200 W
Coolant temperature rise10 °C
CoolantWater
Radiator capacity per 120 mm section100 W
Results
Coolant flow1.73 L/mincalculated
Mass flow0.029 kg/scalculated
Radiator sections (120 mm)12Rule of thumb

Methodology

Energy balance: Q = ṁ × c_p × ΔT. Volumetric flow = ṁ ÷ ρ. Glycol mixtures have lower heat capacity than water, so they need more flow for the same heat and ΔT.

Formulas

Flow
V̇ = Q ÷ (ρ × c_p × ΔT)

Assumptions

  • Approximate coolant properties near 20 °C.

Limitations

  • Radiator sizing is a rule of thumb for desktop loops, not facility heat-exchanger design.