Liquid Cooling & Radiator Sizing Calculator
Calculate the coolant flow needed to absorb a heat load at a chosen coolant temperature rise, for water or glycol mixtures, and estimate radiator size for workstation loops.
Results
- Coolant flow
- 1.73 L/mincalculated
- Mass flow
- 0.029 kg/scalculated
- Radiator sections (120 mm)
- 12Rule of thumb
Pump head and pressure drop are not calculated; check that the pump delivers the flow at the loop's pressure drop.
What it calculates
- Coolant flow rate (L/min)
- Mass flow
- Radiator sections (rule of thumb)
Worked example
Using the default inputs below; change any input above to recalculate.
| Heat load | 1200 W |
|---|---|
| Coolant temperature rise | 10 °C |
| Coolant | Water |
| Radiator capacity per 120 mm section | 100 W |
| Coolant flow | 1.73 L/min | calculated |
|---|---|---|
| Mass flow | 0.029 kg/s | calculated |
| Radiator sections (120 mm) | 12 | Rule of thumb |
Methodology
Energy balance: Q = ṁ × c_p × ΔT. Volumetric flow = ṁ ÷ ρ. Glycol mixtures have lower heat capacity than water, so they need more flow for the same heat and ΔT.
Formulas
- Flow
- V̇ = Q ÷ (ρ × c_p × ΔT)
Assumptions
- Approximate coolant properties near 20 °C.
Limitations
- Radiator sizing is a rule of thumb for desktop loops, not facility heat-exchanger design.