Thermal Headroom Calculator
Use a cooler's thermal resistance to estimate component temperature at a given power and ambient temperature, the remaining headroom, and how ambient temperature changes it.
Results
- Estimated temperature
- 72 °Cestimated
- Headroom
- 23 °Cestimated
- Maximum sustainable power
- 433 Westimated
| Ambient | Temperature | Max power |
|---|---|---|
| 20 °C | 62 °C | 500 W |
| 25 °C | 67 °C | 467 W |
| 30 °C | 72 °C | 433 W |
| 35 °C | 77 °C | 400 W |
| 40 °C | 82 °C | 367 W |
What it calculates
- Estimated temperature
- Thermal headroom
- Maximum sustainable power
- Ambient impact table
Worked example
Using the default inputs below; change any input above to recalculate.
| Component power | 280 W |
|---|---|
| Thermal resistance (component to air) | 0.15 °C/W |
| Ambient / inlet temperature | 30 °C |
| Maximum allowed temperature | 95 °C |
| Estimated temperature | 72 °C | estimated |
|---|---|---|
| Headroom | 23 °C | estimated |
| Maximum sustainable power | 433 W | estimated |
Methodology
Steady-state temperature rise is power × thermal resistance: T = T_ambient + P × θ.
Formulas
- Temperature
- T = T_a + P × θ
- Max power
- P_max = (T_max − T_a) ÷ θ
Assumptions
- Linear thermal resistance; steady state.
Limitations
- Thermal resistance varies with fan speed and power density.