Rack Power & Density Calculator
Total the power of a rack's equipment, convert it to current on single- or three-phase supply, size A/B redundant PDU feeds with continuous-load derating, and report rack density and heat.
Results
- Rack IT load
- 12.6 kWcalculated
- Current per phase
- 19.1 Acalculated
- Minimum PDU rating per feedEach feed sized to carry the full load
- 32 A three-phasecalculated
- PDUs
- 2 (A + B)calculated
- Heat output
- 42,993 BTU/hcalculated
What it calculates
- Rack IT load and density
- Current per phase / feed
- Minimum PDU rating
- Heat output
Worked example
Using the default inputs below; change any input above to recalculate.
| Servers (type 1) | 4 |
|---|---|
| Max power per server (type 1) | 3000 W |
| Servers (type 2) | 0 |
| Max power per server (type 2) | 800 W |
| Switches and other equipment | 600 W |
| Supply | Three-phase 400 V |
| Power factor | 0.95 |
| Continuous-load derating | 80 % |
| A/B redundant feeds | Yes |
| Rack IT load | 12.6 kW | calculated |
|---|---|---|
| Current per phase | 19.1 A | calculated |
| Minimum PDU rating per feed | 32 A three-phase | calculated |
| PDUs | 2 (A + B) | calculated |
| Heat output | 42,993 BTU/h | calculated |
Methodology
Single-phase current I = P ÷ (V × PF). Three-phase line current I = P ÷ (√3 × V_LL × PF). PDUs are sized so continuous current stays within the derating limit (80% is common practice). With A/B feeds each feed must carry the full rack load if the other fails.
Formulas
- Three-phase
- I = P ÷ (√3 × 400 V × PF)
- Single-phase
- I = P ÷ (230 V × PF)
Assumptions
- Balanced load across phases.
- Nameplate maximum power used for servers.
Limitations
- Follow local electrical codes; this is planning arithmetic, not an electrical design.