Rack Power & Density Calculator

Total the power of a rack's equipment, convert it to current on single- or three-phase supply, size A/B redundant PDU feeds with continuous-load derating, and report rack density and heat.

Results

Rack IT load
12.6 kW
Current per phase
19.1 A
Minimum PDU rating per feedEach feed sized to carry the full load
32 A three-phase
PDUs
2 (A + B)
Heat output
42,993 BTU/h

What it calculates

  • Rack IT load and density
  • Current per phase / feed
  • Minimum PDU rating
  • Heat output

Worked example

Using the default inputs below; change any input above to recalculate.

Inputs
Servers (type 1)4
Max power per server (type 1)3000 W
Servers (type 2)0
Max power per server (type 2)800 W
Switches and other equipment600 W
SupplyThree-phase 400 V
Power factor0.95
Continuous-load derating80 %
A/B redundant feedsYes
Results
Rack IT load12.6 kWcalculated
Current per phase19.1 Acalculated
Minimum PDU rating per feed32 A three-phasecalculated
PDUs2 (A + B)calculated
Heat output42,993 BTU/hcalculated

Methodology

Single-phase current I = P ÷ (V × PF). Three-phase line current I = P ÷ (√3 × V_LL × PF). PDUs are sized so continuous current stays within the derating limit (80% is common practice). With A/B feeds each feed must carry the full rack load if the other fails.

Formulas

Three-phase
I = P ÷ (√3 × 400 V × PF)
Single-phase
I = P ÷ (230 V × PF)

Assumptions

  • Balanced load across phases.
  • Nameplate maximum power used for servers.

Limitations

  • Follow local electrical codes; this is planning arithmetic, not an electrical design.