Power Redundancy Calculator
Size power supplies, UPS modules or PDUs for a redundancy scheme and see each unit's load in normal operation and after a failure.
Results
- Units required (N)
- 2calculated
- Units installed (N+1)
- 3calculated
- Installed capacity
- 60 kWcalculated
- Load per unit, normal
- 50%calculated
- Load per unit after one failure
- 75%calculated
- Unit failures tolerated
- 1calculated
What it calculates
- Units required
- Installed capacity
- Load per unit (normal)
- Load per unit after failure
Worked example
Using the default inputs below; change any input above to recalculate.
| Load | 30 kW |
|---|---|
| Capacity per unit | 20 kW |
| Scheme | N+1 |
| Units required (N) | 2 | calculated |
|---|---|---|
| Units installed (N+1) | 3 | calculated |
| Installed capacity | 60 kW | calculated |
| Load per unit, normal | 50% | calculated |
| Load per unit after one failure | 75% | calculated |
| Unit failures tolerated | 1 | calculated |
Methodology
N is the number of units needed to carry the load. N+x adds x spare units; 2N duplicates the full set (two independent paths); 2N+1 adds one more.
Formulas
- N
- N = ⌈load ÷ unit_capacity⌉
Assumptions
- Load is shared equally across healthy units.
Limitations
- 2N assumes independent distribution paths; shared upstream components remain single points of failure.