Data centre cooling basics: heat load, airflow and PUE

Convert IT power into BTU/h and tons of refrigeration, size airflow for a rack, and understand power usage effectiveness.

GIRIVON Engineering · Updated 19 Nov 2026 · 1 min read

Almost every watt consumed by IT equipment becomes heat that the cooling system must remove.

Heat load units

  • 1 W = 3.412 BTU/h
  • 1 ton of refrigeration (TR) = 12,000 BTU/h ≈ 3.517 kW

A 40 kW IT load produces about 136,500 BTU/h ≈ 11.4 TR, before UPS losses, lighting and people.

Airflow for a rack

Air carries heat according to Q = ṁ × c_p × ΔT. At sea level, with air density ≈ 1.2 kg/m³ and c_p ≈ 1,005 J/(kg·K), a 12 kW rack with a 12 °C inlet-to-outlet rise needs:

12,000 ÷ (1.2 × 1,005 × 12) ≈ 0.83 m³/s ≈ 2,990 m³/h (≈ 1,760 CFM).

Halve the temperature rise and the airflow doubles. Thinner air at altitude needs more volume for the same heat.

Inlet temperature

ASHRAE's recommended envelope for IT equipment inlet air is 18–27 °C. Running colder wastes energy; running hotter reduces component headroom.

When air is not enough

Dense GPU racks commonly exceed what room air can remove. Containment, rear-door heat exchangers and direct liquid cooling move heat far more efficiently: water's volumetric heat capacity is roughly 3,500 times that of air.

PUE

Power usage effectiveness = total facility energy ÷ IT equipment energy. A PUE of 1.5 means 0.5 kW of overhead — mostly cooling — for every 1 kW of IT. Facility power, electricity cost and cooling capacity all scale from IT load × PUE.

Plan a room with the Cooling & Heat Load Calculator and a data hall with the Data Centre Planner.